Biến tần Yaskawa CIMR-AT4A0072FKA, 400V 3-phase, 30 KW
Mã sản phẩm:
CIMR-AT4A0072FKA
Brand:
Yaskawa
- Input power supply voltage: 400 V 3-phase
- Customized Specifications: Standard mode
- Protection Design: NEMA Type 1
- Environmental specification: Gas resistant
0
People watching this product now!
Phương thức thanh toán:

Mô tả
Thông tin chung Biến tần Yaskawa CIMR-AT4A0072FKA
– Series: CIMR-AT1000 Series
– Region code: Asia (Singapore and Taiwan)
– T: Asia (Singapore and Taiwan)
– A: Japan
– B: China
– C: Europe
– D: India
– K: Korea
– U: the Americas
– Input power supply voltage: 400 V 3-phase
– Rated Output Current: Check specification & datasheet
– Customized Specifications: Standard mode
– Protection Design: NEMA Type 1
– Environmental specification: Gas resistant
Thông sỗ kỹ thuật Biến tần Yaskawa CIMR-AT4A0072FKA
– Maximum Applicable Motor Capacity (kW) HD Rating <1>: 30
– Maximum Applicable Motor Capacity (kW) HD Rating ND Rating <1> : 37
– Input Current (A): HD Rating <2>: 58
– Input Current (A): ND Rating <2>: 71
– Rated Voltage Rated Frequency: Three-phase 380 to 480 Vac 50/60 Hz/510 to 680 Vdc <3>
– Allowable Voltage Fluctuation: -15 to 10%
– Allowable Frequency Fluctuation: ±5%
– Input Power HD Rating (kVA): 53
– Input Power HD Rating ND Rating (kVA): 65
– Rated Output Capacity HD Rating (kVA) <4>: 46
– Rated Output Capacity ND Rating (kVA) <4>: 55
– Rated Output Current HD Rating <5> (A): 60
– Rated Output Current ND Rating <6> (A): 72
– Overload Tolerance: HD Rating: 150% of rated output current for 60 s (Derating may be required for applications that start and stop frequently) ND Rating: 120% of rated output current for 60 s
– Carrier Frequency: User adjustable between 2 and 15 kHz
– Maximum Output Voltage (V): Three-phase 380 to 480 Vac (proportional to input voltage)
– Maximum Output Frequency (Hz): 400 Hz (user-adjustable)
Thông tin bổ sung
Brand | |
---|---|
Series |
A1000 Series |
Input voltage |
400V 3-phase |
Motor power (KW) |
30 |
Customized Specifications |
Standard mode |
Protection Design |
NEMA 1 |
Environmental |
Gas-resistant |
Download